Features:
•Multifunction Keypad
•Display - Backlit LCD
•Visual and audible alarms
•Monitoring via PC
•Programmable time delays and setpoints
•All readings are field programmable for Metric
or US values
•Write protected set points
•High / low pressure automatic reset
•Alarm silence
•Nonmetallic NEMA 4X enclosure
•Panel or frame mount
•Plug in terminal strips
Standard functions of the ROTrol II are to monitor and / or
control:
•RO and auxiliary pump control relays
•Feed water solenoid valve
•Low feed pressure switch
•High pump pressure switch
•Permeate TDS / Conductivity
•Permeate temperature
•Membrane flush solenoid valve
•RO storage tank full switch
•RO storage tank low switch
•Pretreatment lockout
•Operating hours
•RO tank full override
Optional End Devices and Accessories:
•IEC motor starters and control transformers
for motors above 1 HP.
•Pressure sensors allowing display on LCD of
pressures and differential pressure with programmable setpoint for high,
low, and differential pressure alarms
•Feed TDS / Conductivity sensor with TDS / Conductivity
and % rejection displayed, with alarm setpoints
•Flow sensors for permeate, reject, and recirculate
flow in GPM, LPM, with gallons and % recovery displayed, and alarm setpoints
for low or high flow rates
•pH sensor with pH displayed, with alarm setpoints
•Relay output for permeate divert or *external
alarm
•UL and C-UL listed
*Serial communication port for data acquisition, remote monitoring,
and remote alarms
**Computer link for monitoring via PC
* An external alarm relay is NOT required if the ROTrol II is connected
to the R&D Specialties RA-1 or one channel of the RA-6 Remote Alarm
(see Remote Alarms / Annunciators)
** See the ROTrol II Communications page for details concerning data
acquisition, remote display, and computer monitoring options.
Specifications
Power:
120 VAC, Optional 240 VAC, -15 + 10%, 50 / 60 Hz, 6 Watts
Environment:
-22 F to 140 F, 0 - 95% RH, Noncondensing
Enclosure:
12" x 10" x 6" (305 mm x 254 mm x 152 mm) NEMA 4X
For RO pumps requiring larger than 1 HP, a larger enclosure is offered
to accept motor starters and control transformers
Display:
4 line x 20 character Backlit LCD
Switch inputs:
•Low feed pressure
•High pump pressure
•Tank full / pump OFF
•Tank full / pump ON
•Tank low
•Pretreat lockout
TDS / Conductivity Sensor:
•Permeate, 0-250 PPM or 0-250 uS, temperature
compensated (other ranges available)
•Wetted parts ABS and 316 SS, 300 PSI Max, 3/4"
NPT
•Permeate temperature 0-150 F / 0-65 C
Control Relays:
•RO pump control, 1 HP Max, 120/240 VAC
•Auxiliary pump control, 1 HP Max, 120/240 VAC
•Inlet Valve, 5 AMP Max, 120/240 VAC
•Flush Valve, 5 AMP Max, 120/240 VAC
Time Delays:
User programmable
Optional Sensor Inputs:
•Feed TDS / Conductivity standard range 0-2500
(other ranges available)
•Feed pressure, 0-125 PSI , ABS / 316 SS, 1/4"
NPT
•Pump pressure, 0-400 or 0-1500 PSI, ABS / 316
SS, 1/4" NPT
•Pre-filter differential pressure, 0-125 PSI
•Membrane differential pressure, 0-400 or 0-1500
PSI
•pH, range 0-12, ABS, 150 PSI, 3/4" NPT
•Permeate, reject, re-circulate flow sensors
(per specification)
|