Series 100

Light Commercial RO Controller

Instructions

The Series 100 microprocessor controller is an ideal solution for the monitoring and control of light commercial reverse osmosis units. This economical controller provides relays for the RO pump, inlet solenoid valve, and membrane flush solenoid valve.


The dry contact switch inputs will monitor storage tank level, low and/or high pressure switch signal, and system lockout for pretreatment backwash or regeneration for on/off operation. All inputs and outputs are controlled with time delays for proper operation.


The Series 100 features a digital display readout of the permeate TDS with a temperature compensated cell. Additionally the TDS value incorporates a field adjustable set point for water quality threshold, allowing the unit to produce a system warning if the water quality threshold is exceeded. The Series 100 RO controller has two red/green LED’s to indicate water quality and operating status.

Features: Proven reliability for over 15 years
•Economical controls
•Visual status LED
•TDS monitor w/ sensor (range 0-1000 PPM)
•Three digit LED display
•Jumper selectable flush types
•Jumper selectable switch inputs
•TDS calibration adjustment
•TDS set point adjustment
•Quick disconnect high voltage terminals
•Plug in terminals for switch inputs
•Panel mountable enclosure

Series 100 Specifications:

Power
120 VAC or 240 VAC, -15+10% 50/60Hz


Environment
-22 to 140F, 0-95%RH, Noncondensing


Enclosure
8.25” x 5.0” x 3.0” ABS plastic


Inputs/Outputs
Switch Inputs:

• Low pressure switch
• RO storage tank full
• Pretreatment Lockout


(All switch inputs are jumper selectable NO or NC)

Control Relays:
• Inlet Solenoid valve 120/240 VAC 5 amp maximum


• RO pump 120/240 VAC 1HP, single phase maximum


• Flush solenoid valve 120/240 VAC 5 amp maximum


Options:
Wire Harness Kit: